Rate Schedule
SCHEDULE CP
CONTRACT INDUSTRIAL SERVICE
12.06.260
A. AVAILABILITY:
For major industrial power use upon the execution of a written Power Service
Agreement (Contract) with Tacoma Power, which shall require among other
conditions:
- A minimum Contract Demand (as set forth in the Contract) of not
less than 8,000 kilowatts;
- Delivery of power at one primary voltage;
- Metering at primary voltage but in no case at less than nominal
4,160 volts;
- Power factor adjustment to 95 percent lagging or better; and
- Service is subject to curtailment and certain notice provisions
are applicable.
|
|
B. MONTHLY RATE:
The sum of the following power service, delivery, customer and other charges:
1. Power Service Charges:
|
(a) Energy:
| All Contract Energy (as set forth in the Contract) measured in
kilowatt-hours at $0.023564 per kWh. |
|
(b) Demand:
All kilowatts of Billing Demand delivered at $3.77 per kW.
|
|
| (c) Minimum Charge:
|
|
(d) Contract Energy Overrun:
|
All energy measured in excess of the Contract Energy (as set forth in the
Contract) is subject to a Contract Energy Overrun charge, pursuant to the
following formula:
Contract Energy Overrun Charge = (MWh + Losses) x (THI + Tx) x 120%
where:
|
MWh =
|
the aggregate MWh over the day the customer’s total
measured daily load was above the Contract Energy amount; |
|
Losses = |
MWh x 1.9%; |
| THI = |
the highest hourly price observed on the Tacoma Hourly
Index
within the day of overrun; |
| Tx = |
applicable BPA or successor organization, transmission rate
in $
per MWh. |
|
(e) Contract Demand Overrun:
|
A Contract Demand Overrun charge shall be imposed when the total
measured demand (highest 30-minute integrated demand) exceeds the
Contract Demand (as set forth
in the Contract). Said charge is pursuant to
the following formula:
Contract Demand Overrun Charge = MW x 300% x DC
where:
MW = MW of metered Demand in excess of the
Contract Demand;
DC = Demand Charge.
|
|
|
|
2. Delivery:
|
All kilowatts of Billing Demand delivered at $3.90 per kW. |
|
3.
Customer Charge:
|
$760.00 per month or
any fraction thereof. |
|
4.
Exceptions:
|
(a) Within the
City of Fife:
|
(1) Power Service
Charges:
|
(i) Energy:
All Contract Energy
(as set forth in the Contract) measured in
kilowatt-hours at $0.024375 per kWh. |
|
(ii)
Demand:
All kilowatts of
Billing Demand delivered at $3.90 per kW.
|
|
(iii)
Minimum Charge:
The Demand Charge.
|
|
(iv) Contract
Energy Overrun:
All energy measured in excess of the Contract Energy (as
set forth in the Contract)
is subject to a Contract Energy Overrun charge, pursuant to the following formula:
Contract Energy Overrun Charge = (MWh + Losses) x (THI + Tx) x 124.1319%
where:
| MWh =
|
the aggregate MWh over the day the customer’s total
measured daily load was above the Contract Energy amount; |
| Losses = |
MWh x 1.9%; |
| THI = |
the highest hourly price observed on the Tacoma Hourly
Index
within the day of overrun; |
| Tx = |
applicable BPA or successor organization, transmission rate
in $
per MWh. |
|
|
(v) Contract Demand Overrun:
A Contract Demand Overrun charge shall be imposed when the total
measured demand (highest 30-minute integrated demand) exceeds the
Contract Demand (as set forth in the Contract). Said charge is
pursuant to the following:
Contract Demand Overrun Charge = MW x 300% x DC
where:
MW = MW of metered Demand in excess of the Contract
Demand;
DC = Demand Charge.
|
|
|
(2) Delivery:
All kilowatts of Billing Demand delivered at $4.03 per
kW. |
|
(3) Customer Charge:
$786.17 per month or any fraction thereof. |
|
|
C. BILLING DEMAND:
Determined by means of a demand meter, 30-minute interval, reset monthly.
- The Billing Demand shall be the highest of:
(a) The highest measured demand for the month, adjusted for power factor;
(b) 60 percent of the highest measured demand occurring during any of the
preceding 11 months after adjustment for power factor,
(c) A demand level equal to the Contract Energy, in average megawatts (as set
forth in the Contract); or
(d) 60 percent of the highest Contract Demand (as set forth in the Contract)
during any of the preceding 11 months.
D. SUBSTATION CREDIT:
For customers who provide all of their own transformation from Tacoma
Power’s transmission system voltage, a credit of
14.43 percent will be applicable to the
delivery charge.
E. SERVICE CONDITIONS:
- Power factor provision applicable; and
- Applicable provisions of the Tacoma Municipal Code, General
Provisions, and Customer Service Policies governing the sale of
electric energy and delivery services shall apply.
|
|